← Manufacturing
Step 09 Facility Infrastructure

N₂ Gas Supply / LN₂ Dewar System

Airgas / Chart Industries MVE 160 HIGH ● 4+ process tools require continuous N₂ supply; cannot fabricate without it

Role in QLT Fabrication

Gas Requirements by Tool

ToolN₂ PurposeFlow RatePressurePurity
ICP-RIE (#01)Chamber purge, leak check5–10 L/min (intermittent)20 PSI99.999% (UHP)
ALD (#23)Carrier gas, purge5 L/min (continuous during deposition)20 PSI99.999%
PECVD (#24)Carrier gas5 L/min (continuous)20 PSI99.999%
Sputterer (#25)Chamber backfill2 L/min (intermittent)20 PSI99.999%
Glove Box (#35)Inert atmosphere, antechamber purge5–50 L/min (antechamber cycles)55 PSI99.99%
Fume hood / generalAtmosphere controlVariableLow99.99%
General bench useBlow-dry samples< 1 L/min20 PSIIndustrial OK
Wire bonder (#31)Bond head purge< 1 L/min5 PSI99.99%

Total Consumption Estimate

CategoryDaily Use (L/min avg × hours)Daily Volume
Process tools (ALD + PECVD + RIE)~15 L/min × 4 hr active3,600 L
Glove box (antechamber cycles)~10 L/min × 2 hr1,200 L
General purge, sample dry~2 L/min × 8 hr960 L
Total daily~5,800 L/day (~5.8 m³/day)
Monthly~120 m³

At 120 m³/month, K-cylinders (6.5 m³ each) would require ~18 cylinders/month ● impractical and expensive.

→ Bulk LN₂ dewar is the cost-effective solution for sustained operations.

Technical Specifications

ToolN₂ PurposeFlow RatePressurePurity
ICP-RIE (#01)Chamber purge, leak check5–10 L/min (intermittent)20 PSI99.999% (UHP)
ALD (#23)Carrier gas, purge5 L/min (continuous during deposition)20 PSI99.999%
PECVD (#24)Carrier gas5 L/min (continuous)20 PSI99.999%
Sputterer (#25)Chamber backfill2 L/min (intermittent)20 PSI99.999%
Glove Box (#35)Inert atmosphere, antechamber purge5–50 L/min (antechamber cycles)55 PSI99.99%
Fume hood / generalAtmosphere controlVariableLow99.99%
General bench useBlow-dry samples< 1 L/min20 PSIIndustrial OK
Wire bonder (#31)Bond head purge< 1 L/min5 PSI99.99%
CategoryDaily Use (L/min avg × hours)Daily Volume
Process tools (ALD + PECVD + RIE)~15 L/min × 4 hr active3,600 L
Glove box (antechamber cycles)~10 L/min × 2 hr1,200 L
General purge, sample dry~2 L/min × 8 hr960 L
Total daily~5,800 L/day (~5.8 m³/day)
Monthly~120 m³
ParameterSpecification
Cylinder sizeT (standard, 6,500 L at STP) or K (5,700 L)
Purity99.999% (Grade 5, UHP)
Pressure2,200 PSI (full)
Price per cylinder$50–$100 (gas) + $10–$20/month rental
Cylinders per month (at 120 m³/month)~18 ● impractical for sustained use
Cylinders per month (initial R&D at 30 m³/month)~5 ● manageable
Monthly cost (initial R&D)$400–$700 (gas + rental)
DeliverySame-day (Airgas local) or next-day
SpaceCylinder rack (4–8 cylinders, manifolded)
ParameterSpecification
DewarChart MVE 160/195 or Airgas Microbulk
Capacity160 L LN₂ → ~130 m³ N₂ gas (at STP)
Refill cycleEvery 3–4 weeks at QLT R&D consumption
Gas output1–15 L/min from dewar head; regulated to 20 PSI
Purity99.999% (inherently from LN₂ vaporization)
Price per fill$100–$200
Monthly cost$200–$400
Annual cost$2,500–$5,000
DeliveryAirgas scheduled refills; dewar loaner/rental program
SpaceFloor footprint ~0.5 m × 0.5 m
SafetyLN₂ cryogenic hazard; O₂ monitor required

Process Integration

Initial Setup (K-Cylinder Configuration)

  • Install cylinder rack in ventilated area (outdoor wall or inside lab with ventilation)
  • Secure 4 cylinders to wall with chains or rack restraints
  • Install 4-cylinder automatic switchover manifold
  • Connect 2-stage UHP regulator at manifold outlet; set delivery to 60 PSI
  • Run 1/4" stainless tubing from manifold to each tool location
  • Install point-of-use regulators at each tool (set to 20 PSI typical)
  • Pressure test all connections; check with snoop (leak detection soap)
  • Install O₂ monitor in lab room ● MANDATORY safety equipment
  • Open cylinder valves ● verify pressure at each POU regulator
  • System operational ● begin process tool commissioning

Transition to Bulk LN₂ Dewar

  • Contact Airgas local office for microbulk LN₂ program
  • Install dewar in lab or adjacent utility area (floor load: ~200 kg full)
  • Connect dewar head to existing gas manifold (dewar replaces cylinders as source)
  • Verify delivery pressure and flow rate
  • Schedule automatic refills with Airgas (every 3–4 weeks)

Vendor Options & Pricing

Supply OptionVendorMonthly CostAnnual CostSetup Cost
K-cylinders (initial R&D)Airgas, Linde, Matheson$400–$700$5,000–$8,500$1,500 (manifold, regulators)
Bulk LN₂ dewar (160L)Airgas microbulk$200–$400$2,500–$5,000$500 (dewar rental)
Nitrogen generator (PSA)Parker, Atlas Copco$40 (electricity)$500$8,000–$15,000 (generator)

Facility Requirements

ParameterSpecification
Cylinder storageOutdoor or ventilated area; chained to wall; away from heat sources
Dewar locationIndoors (lab) or adjacent utility area; adequate ventilation
Gas lines1/4" stainless or copper tubing; pressure-tested at 1.5× working pressure
Regulators2-stage, UHP-rated, CGA 580 ($200–$500 each); need 1 per manifold + 1 per tool
O₂ monitorMANDATORY ● wall-mounted with audible + visual alarm at 19.5% O₂
Manifold4-cylinder automatic switchover manifold ($500–$1,500)
VentilationAdequate room ventilation (ACH ≥ 6 recommended for labs with gas systems)
SignageN₂ gas hazard sign at each cylinder/dewar location
Emergency shutoffQuarter-turn ball valve at manifold outlet for emergency gas shutoff

Safety & Handling

HazardRiskMitigation
Asphyxiation (N₂ displaces O₂)HIGH in small roomsO₂ monitor MANDATORY; alarm at < 19.5% O₂; never work alone with large N₂ release
LN₂ cryogenic burnsMEDIUM (when handling dewar)Cryo-rated gloves; face shield; training
High-pressure cylinder ruptureVERY LOWSecure to wall with chains; never drop; use proper regulator; inspect annually
Cylinder fallsMEDIUMChain/strap all cylinders; use approved cylinder carts for transport
Gas line leakLOWPressure test on installation; periodic leak check with snoop

Emergency Procedures

ScenarioAction
O₂ monitor alarm soundsEvacuate room immediately; open doors/windows; do NOT re-enter until O₂ > 19.5%
LN₂ spill from dewarEvacuate area; ventilate; LN₂ will evaporate ● O₂ displacement is the hazard
Cylinder leak (hissing sound)Close cylinder valve if safe; evacuate if large release; ventilate room
Person collapses near N₂ sourceDrag to fresh air; call 911; begin CPR if not breathing; do NOT enter O₂-depleted area
← Back to Manufacturing
QLT

Protected Equipment Data

This page contains proprietary manufacturing specifications. Enter access code to continue.

Request Access →